JUSTIFICATION OF THE METHOD OF MATCHING OF FIRE RESISTANCE LIMIT OBTAINED DURING OF THE FIRE TEST TO THE FIRE RESISTANCE LIMIT ACCORDING TO THE STANDARD TEMPERATURE MODE

Authors

  • Роман Веселівський Lviv State University of Life Safety

DOI:

https://doi.org/10.33269/nvcz.2021.1(11).56-63

Keywords:

matching, fire resistance limit, area comparison method, standard temperature mode, heating temperature, heat-insulating ability

Abstract

Ways and experience of application of various methods concerning the matching of a limit of fire resistance of building constructions in case of deviation of a temperature mode of fire test from a standard temperature mode of a fire have been analyzed. On the basis of theoretical and experimental researches, the comparison of real and standard temperature effects was performed using the method of comparing the areas under the fire curve and limited by the ordinate of temperature, which achieved one of the criteria of fire resistance and abscissa. The adequacy of the method of matching the limit of fire resistance was checked by analytical calculation using the Green's function. It is established that the method of matching the real temperature obtained as a result of the fire test to the standard temperature mode of the fire is adequate and can be used in engineering calculations that provides accuracy within 10-15%.

Published

2021-07-02

How to Cite

Веселівський, Р. (2021). JUSTIFICATION OF THE METHOD OF MATCHING OF FIRE RESISTANCE LIMIT OBTAINED DURING OF THE FIRE TEST TO THE FIRE RESISTANCE LIMIT ACCORDING TO THE STANDARD TEMPERATURE MODE. Scientific Bulletin: Civil Protection and Fire Safety, (1(11), 56–63. https://doi.org/10.33269/nvcz.2021.1(11).56-63